The Guide To Good
WORKMANSHIP
An engineer handbook containing Telko product installation guidelines
Installation of Telko Products:
Server (2224 C):
Ground Server
Ground power cable shield
Use cable markings
Use bolt, washer and nut when mounting
Use wire markings
Add some extra cable before connecting to the contacts on the Server
Displays:
Ground Display
Ground power cable shield
Use cable markings
Use bolt, washer and nut when mounting
Keyboard/Trackball:
Use cable markings
Use cable ties so nothing will come loose due to vibrations
Interface:
Ground Unit
Ground power cable shield
Use cable markings
Use bolt, washer and nut when mounting
Use wire markings
Groundings:
Always ground all units and power cables with ground wire. It is especially important when units are mounted on wood, plastic or other non-conductive material. For power cables, use ground wire in cable and also cable shield.
If grounding NMEA cables:
-
Best: ground the transmitting end of the cable only
-
Next-best: ground the receiving end of the cable only
-
Worst: ground both ends of the cable
Networks:
A-A: The T-568A standard is supposed to be used in new network installations. Most off-the-shelf Ethernet cables are still of the T-568B standard, however, it makes absolutely no functional difference which one you choose.
B-B: Both the T-568A and the T-568B standard Straight-Through cables are used most often as patch cords for your Ethernet connections. If you require a cable to connect two Ethernet devices directly together without a hub or when you connect two hubs together, you will need to use a Crossover cable instead.
A-B: A good way of remembering how to wire a Crossover Ethernet cable is to wire one end using the T-568A standard and the other end using the T-568B standard. Another way of remembering the color coding is to simply switch the Green set of wires in place with the Orange set of wires. Specifically; switch the solid Green (G) with the solid Orange, and switch the green/white with the orange/white.
-
ALWAYS test any self-made network cables with cable tester
-
Halogen free Network cable Max length 100m
Cables:
- 2x2,5
- Halogen free power 24V DC
- 3G1,5
- Halogen free power 240V AC
- 2x2x0,5
- Halogen free signal (Nmea, Analog)
- USB
- Network Cat5, Cat5e, Cat6
- Halogen free network
- VGA
- Use the included standard length
Power:
If units are connected to 24 V DC Source
Amp |
Watt |
Max length area 1,5 |
Max length area 2,5 |
Max length area 4 |
0,5 |
12 |
70m |
120m |
|
0,75 |
18 |
50m |
80m |
|
1 |
24 |
30m |
60m |
|
1,50 |
36 |
X |
40m |
60m |
2 |
48 |
X |
30m |
50m |
2,50 |
60 |
X |
23m |
45m |
3 |
72 |
X |
20m |
35m |
3,50 |
84 |
X |
17m |
30m |
4 |
96 |
X |
15m |
25m |
4,50 |
108 |
X |
13m |
22m |
5 |
120 |
X |
12m |
20m |
5,50 |
132 |
X |
10m |
17m |
6 |
144 |
X |
9m |
15m |